SIL Verification Tool
Verify PFDavg against IEC 61511 SIL requirements for any SIS architecture. Enter your details to unlock — no spam, ever.
1oo1, 1oo2, 2oo2, 2oo3 architectures
PFDavg per IEC 61511
Common cause factor (β)
Diagnostic coverage (DC)
SIL achieved vs. required
Architecture comparison table
Please enter a valid email address.
Skip for now
🔒 No spam. No sales calls unless you ask. Your email is used only to send occasional process safety resources from SafeGuard Projects.
SAFEGUARD FAMILY  ·  SafeGuard PSM  ·  SafeGuard Projects  ·  OSHA1910119.com
Free Tool — Email Required

SIL
Verification Tool

Calculate PFDavg for your Safety Instrumented System and verify whether it meets the required Safety Integrity Level per IEC 61511. Supports 1oo1, 1oo2, 2oo2, 2oo3, and 1oo2D architectures with common cause and diagnostic coverage.

IEC 61511 / ISA-84 1oo1 / 1oo2 / 2oo2 / 2oo3 Common Cause (β) Diagnostic Coverage (DC) Architecture Comparison Print Report
IEC 61511 SIL PFDavg Ranges
SIL 10.01 – 0.1
SIL 20.001 – 0.01
SIL 30.0001 – 0.001
SIL 4< 0.0001
PFDavg = λDU × TI/2 (1oo1)simplified
📋
Safety Instrumented Function
Describe the SIF being verified
SIF Description
Required SIL
🏗️
SIS Architecture
Voting configuration for sensors, logic solver, and final elements
Voting Architecture (applies to each subsystem independently)
📉
Failure Rate Parameters
Per IEC 61508 / SIL Tier 2 assessment data
Total Dangerous Failure Rate (λD) /hr
Typical values: transmitter 1×10⁻⁶/hr, valve 2×10⁻⁶/hr, logic solver 1×10⁻⁷/hr. Source from SIL Tier 2 assessment or EXIDA/SIS-TECH data.
Diagnostic Coverage (DC) 0–1
DC = fraction of dangerous failures detected by online diagnostics. Drives the split between λDD (detected) and λDU (undetected).
Proof Test Interval (TI) years
Common Cause Factor (β) for redundant architectures
β is the fraction of failures that affect all redundant channels simultaneously. Ignored for 1oo1 — only applies to 1oo2, 2oo2, 2oo3.
Mission Time (TM) years — typically 20 years per IEC 61511
⚖️
Architecture Comparison
PFDavg for all architectures with current failure rate parameters
ArchitecturePFDavgSIL AchievedStatus vs. SIL 2
SIL Verification Result
New SIF
Calculated PFDavg
Enter parameters above
AWAITING INPUT
Enter λD and proof test interval to verify
Required SIL
SIL 2
PFDavg 0.001–0.01
SIL Achieved
Calculation Breakdown
Enter parameters to see calculation

Architecture 1oo1
λDU (undetected dangerous)
Proof Test Interval
📚 IEC 61511 Reference — Failure Rate Data & PFD Formulas
Typical Dangerous Failure Rates (λD)
ComponentλD (/hr)
Pressure transmitter1×10⁻⁶
Temperature transmitter5×10⁻⁷
Level transmitter2×10⁻⁶
Flow transmitter1×10⁻⁶
Pressure switch3×10⁻⁶
Solenoid valve5×10⁻⁷
Control valve (SIL-rated)2×10⁻⁶
Logic solver / PLC (SIL-rated)1×10⁻⁷
Relay (safety rated)1×10⁻⁷
PFDavg Formulas Used (IEC 61508-6)
ArchitectureSimplified PFDavg Formula
1oo1λDU × TI/2
1oo2(1−β)(λDU·TI)²/3 + β·λDU·TI/2
2oo2λDU × TI
2oo3(1−β)(λDU·TI)² + β·λDU·TI/2
Where λDU = λD × (1 − DC). TI = proof test interval in years. β = common cause factor. Formulas are simplified per IEC 61508-6 Annex B — for full SIL Tier 3 verification use Markov or fault tree analysis.

Need a Full SIL Tier 3 Verification?

This tool provides a Tier 1/2 PFDavg estimate. Formal SIL verification for IEC 61511 compliance requires a Tier 3 assessment — Markov analysis, fault tree, or FMEDA — performed by a qualified functional safety engineer. Our team is TÜV-experienced and has verified SIS across chemical, refinery, and midstream projects.

Talk to Our SIL Team →